Dustin 7b54bc4400 nut-monitor: Require both UPS to be online
Unfortunately, the automatic transfer switch does not seem to work
correctly.  When the standby source is a UPS running on battery, it does
*not* switch sources if the primary fails.  In other words, when the
power is out and both UPS are running on battery, when the first one
dies, it will NOT switch to the second one.  It has no trouble switching
when the second source is mains power, though, which is very strange.

I have tried messing with all the settings including nominal input
voltage, sensitivity, and frequency tolerence, but none seem to have any
effect.

Since it is more important for the machines to shut down safely than it
is to have an extra 10-15 minutes of runtime during an outage, the best
solution for now is to configure the hosts to shut down as soon as the
first UPS battery gets low.  This is largely a waste of the second UPS,
but at least it will help prevent data loss.
2024-01-25 21:22:04 -06:00
Dustin 525f2b2a04 nut-monitor: Configure upsmon
`upsmon` is the component of [NUT] that monitors (local or remote) UPS
devices and reacts to changes in their state.  Notably, it is
responsible for powering down the system when there is insufficient
power to the system.
2024-01-19 20:50:03 -06:00