Dustin 7b54bc4400 nut-monitor: Require both UPS to be online
Unfortunately, the automatic transfer switch does not seem to work
correctly.  When the standby source is a UPS running on battery, it does
*not* switch sources if the primary fails.  In other words, when the
power is out and both UPS are running on battery, when the first one
dies, it will NOT switch to the second one.  It has no trouble switching
when the second source is mains power, though, which is very strange.

I have tried messing with all the settings including nominal input
voltage, sensitivity, and frequency tolerence, but none seem to have any
effect.

Since it is more important for the machines to shut down safely than it
is to have an extra 10-15 minutes of runtime during an outage, the best
solution for now is to configure the hosts to shut down as soon as the
first UPS battery gets low.  This is largely a waste of the second UPS,
but at least it will help prevent data loss.
2024-01-25 21:22:04 -06:00
Dustin 764177daf3 vmhost0: Shut down when first UPS goes low battery
The automatic transfer switch does not seem to work reliably when both
UPS sources are running on battery.  This means all systems lose power
after the first UPS battery dies, even though the second UPS is still
online.  To minimize the risk of data loss, at least until I figure out
what's wrong, I want both VM hosts to shut down as soon as the first UPS
signals that its battery is low.
2024-01-22 08:46:32 -06:00
Dustin 525f2b2a04 nut-monitor: Configure upsmon
`upsmon` is the component of [NUT] that monitors (local or remote) UPS
devices and reacts to changes in their state.  Notably, it is
responsible for powering down the system when there is insufficient
power to the system.
2024-01-19 20:50:03 -06:00
Dustin 57702bb9c7 hosts: vmhost[01]: Update static DNS server address 2022-12-18 20:19:32 -06:00
Dustin 881c8de625 Switch Prometheus/collectd to pull
Transitioning from push-based to pull-based monitoring with
Prometheus/collectd.  The *write_prometheus* plugin will be installed on
all hosts, and Prometheus will be configured to scrape them directly.
2021-10-30 16:41:17 -05:00
Dustin 3f49175c1d host: vmhost0: Set host-specific network config
*vmhost0.pyrocufflink.blue* no longer uses `dhcpcd` for network
configuration, but *systemd-networkd*.

The host-specific network settings for a VM host include the
configuration for the management interface, as well as the configuration
of the physical ports that make up the bonded interfaces.
2021-10-10 16:09:15 -05:00
Dustin 207c9d6428 hosts: vmhost{0,1}: Configure collectd server
The VM hosts have multiple network interfaces with IPv6 addresses, so
collectd may not always choose the correct one to send metrics.  Thus we
have to explicitly tell it to use the management interface, to avoid it
sending data on the SAN interface.
2021-07-24 18:37:18 -05:00
Dustin 11dc40bc76 hosts: Add vmhost{0,1}.p.b 2018-07-23 17:35:10 -05:00